NARTIS-I100
Smart Single-Phase Meter
It is designed to meter active and reactive power in the direct and reverse directions, active and reactive electric power, power grid parameters: RMS values of voltage and AC power, power grid frequency, power factor cosφ, reactive power factor tg, and power quality: voltage underdeviations and overdeviations, deviations of the fundamental power supply voltage frequency from the rated value in single-phase AC power grids with a frequency of 50 Hz.
Nartis-I100 meter fully meets the requirements of:
Nartis-I100 meter meets the requirements for products manufactured in the Russian Federation:
Nartis-I100 meter fully meets the requirements of:
- Decree of the Government of the Russian Federation No. 890 dated June 19, 2020 on Approval of the Rules for Providing Access to the Minimum Set of Functions of Smart Electricity (Power) Meters
- Standard of ROSSETI PJSC
- The exchange protocol meets electronic meter data exchange protocol specifications (GOST R 58940-2020).
Nartis-I100 meter meets the requirements for products manufactured in the Russian Federation:
- NARTIS-I100-W113-2 is included in the Register of the Ministry of Industry and Trade, Conclusion No. 138645/11 dated 21.12.2023
- NARTIS-I100-SP1-2 is included in the Register of the Ministry of Industry and Trade, Conclusion No. 133468/11 dated 11.12.2023
- NARTIS-I100-W112-2 is included in the Register of the Ministry of Industry and Trade, conclusion No. 112843/10 dated 20.10.2023
-
Name characteristic
Value
-
PRICE CURRENCY
RUB
- Communication interfaces: Optoport, RS-485, RF, GSM
- Supported protocols: Electronic Meter Data Exchange Protocol (GOST R 58940-2020), Smart Distributed Systems Protocol (GOST R 59966-2021)
- Electricity metering on a cumulative total basis and separately for all rates
- 8 rate zones
- Built-in load control relay designed for switching the phase current circuit of the meter
- Hardware interlocking of the built-in load control relay
- The flexible programming rater differentiates the amount of electricity consumed according to the created daily, weekly and seasonal patterns
- Up to 12 daily patterns, each of which can include up to 24 rate switching points within a day. Flexibility in setting rate schedules (including working days, weekends, and holidays). Programmable start of billing periods.
- Possibility of switching to summer/winter time
- Storage of readings at the beginning of the day (for 180 days), at the beginning of the month (for 36 months), at the beginning of the year (for 3 years)
- Four-channel power profile with programmable interval from 1 to 60 minutes
- Pulse output, which can be configured to generate telemetry or verification pulses
- Constant and alternating magnetic field sensor
- Ability to send initiative messages
- Availability of logs per GOST R 58940-2020
- The meter can be used as an electricity quality meter per GOST 32144-2013
- Wireless display as an indicator for a split meter with battery power and a micro-USB connector for charging from an external source
- A compartment for a removable communication module in a split meter
- Additional factory-made electronic seals for the terminal cover and meter cover
- It meets the requirements of Decree of the Government of the Russian Federation No. 890 dated June 19, 2020 on Approval of the Rules for Providing Access to the Minimum Set of Functions of Smart Electricity (Power) Meters.
- Meter versions fully meet industry requirements, including the standards of ROSSETI PJSC.
Code structure of possible meter designs
Meter type:
Casing type:
Accuracy class:
Rated voltage:
Base current:
Maximum current:
Number and type of measuring elements:
Main interface:
Additional interfaces:
Supported data transfer protocols:
Additional features:
Number of electricity metering directions:
- NARTIS-I100-2-3-4-6-7-8-9-10-11-12
Meter type:
- NARTIS-I100
Casing type:
- W111 – board-mounted, version 1
- W112 – board-mounted, based on domestic electronic components
- W113 – board-mounted, version 2
- SP1 – OHL pole-mounted, version
Accuracy class:
- A1 – accuracy class 1 per GOST 31819.21
- A1R1 – accuracy class 1 per GOST 31819.21 and accuracy class 1 per GOST 31819.23
Rated voltage:
- 230 – 230 V
Base current:
- 5 – 5 А
Maximum current:
- 60А – 60А
- 80А – 80А
- 100 – 100А
Number and type of measuring elements:
- SS – two shunts in the phase current circuit and neutral current circuit
- ST – shunt in the phase current circuit and a current transformer in the neutral current circuit
- TT – two current transformers in the phase current circuit and in the neutral current circuit
Main interface:
- CAN – CAN interface
- RS485 – RS-485 interface
- RF433/n - 433MHz radio interface, where n is the version number of the interface module
- RF868/n - 868MHz radio interface, where n is the version number of the interface module
- RF2400/n - 2400MHz radio interface, where n is the version number of the interface module
- PL/n - PLC modem, where n is the version number of the interface module
Additional interfaces:
- CAN – CAN interface
- RS485 – RS-485 interface
- RF433/n - 433MHz radio interface, where n is the version number of the interface module
- RF868/n - 868MHz radio interface, where n is the version number of the interface module
- G/n - GSM/GPRS radio interface, where n is the version number of the interface module
- RF2400/n - 2400MHz radio interface, where n is the version number of the interface module
- E/n - Ethernet interface, where n is the version number of the interface module
- PL/n - PLC modem, where n is the version number of the interface module
- RFLT – LTE radio interface
- (No symbol) – no interface
Supported data transfer protocols:
- P1 – DLMS/COSEM/Electronic Meter Data Exchange Protocol, Smart Distributed Systems Protocol
Additional features:
- E – space for a removable expansion module
- H – magnetic field sensor
- In - digital input, where n is the number of inputs
- K – load control relay in the current circuit
- L – indicator light
- M – power grid quality measurement
- O – optical port
- Qn - digital output, where n is the number of outputs
- R – casing unscrewing protection
- U – casing integrity protection
- Vn - electronic seal, where n can take the values:
- 1 – electronic seal on the casing
- 2 – electronic seal on the terminal cover
- 3 – electronic seals on the casing and terminal cover
- Y – protection against replacement of casing parts
- Z/n - backup power source, where n is the version number of the power source
Number of electricity metering directions:
- (No symbol) – electricity metering in one direction (module-based)
- D – electricity metering in two directions
Contact us for service and warranty issues