NARTIS-I500
Smart High-Voltage Electricity Meter
NARTIS-I500 smart high-voltage electricity meter is designed to measure active and reactive electric energy in the forward and reverse directions, and active, reactive and full power, linear voltages, phase currents, grid frequency, specific energy loss in current circuits, forward and reverse current, reverse current unbalance ratio, reactive power factor tgφ, power factor cosφ in three-phase three-wire alternating current power grids with an industrial frequency of 50 Hz with an insulated neutral voltage of 6/10 kV (depending on the design).
The meter is installed on overhead power lines with horizontal wires. The meter can be used autonomously, as part of automated electricity monitoring and metering systems, automated dispatch control systems, or connected to a smart electricity (power) metering system. NARTIS-D101-2 remote digital display is used for remote reading and displaying information from the remote smart electricity meter.
-
Name characteristic
Value
-
PRICE CURRENCY
RUB
- When a remote smart electricity meter is exposed to magnetic fields, a corresponding entry is made in the event log.
- Electricity metering at 8 current rates in accordance with monthly rate zone change programs (the number of monthly programs is up to 12, the number of rate zones per day is 16, the number of rate zones per month is up to 480)
- IP65 per GOST 14254-2015
- Optical port, GOST IEC 61107-2011
- Space for a removable communication module (GSM module)
- Meets the requirements of GOST 31818.11-2012, GOST 31819.22-2012, GOST 31819.23-2012
- Backup communication channel with the information computing system
- Remote smart electricity meters are equipped with a real-time clock with automatic adjustment of settings, which is supported by an integrated lithium battery in the absence of external power supply.
- Each measuring unit is equipped with two SIM card slots
- The measuring units exchange data via Bluetooth interface and have a unique Bluetooth MAC address.
- Functional indicators on the underside of the enclosures of measuring units
Code structure of the module
Meter type:
Casing type:
Accuracy class:
Rated voltage:
Base (maximum) current:
Additional communication interface:
- NARTIS-I500-2-3-4-5-6
Meter type:
- NARTIS-I500
Casing type:
- KnBm, where n is the version number of the casing, m is the version of components
Accuracy class:
- A5SR1, where A5S is accuracy class 0.5S per GOST 31819.22-2012, R1 is accuracy class 1 per GOST 31819.23-2012
Rated voltage:
- 6 kV
- 10 kV
Base (maximum) current:
- 10(100)А
- 10(200)А
Additional communication interface:
- G/n - GSM/GPRS/NB-IoT/LTE radio interface, where n is the version number of the interface module
- RF433/n - 433MHz radio interface, where n is the version number of the interface module
- RF868/n - 868MHz radio interface, where n is the version number of the interface module
- RF2400/n - 2400MHz radio interface, where n is the version number of the interface module
Contact us for service and warranty issues